Power, Safety, Hearing and Production Management
Run an audio system safely: power budgeting and circuit load, three-phase balance, voltage drop in long cable runs, earthing and RCD protection, flown and stacked loads, working-load limits, hearing protection, paperwork such as input lists and stage plots, and calculating currents and loads.
1. Why safety is part of sound engineering
A show has live mains power, heavy loads, cables on the floor and very high sound levels. A good engineer protects the audience, crew and performers as much as the sound.
2. Power basics
Current in amps = power in watts / voltage (for resistive loads; for others divide also by the power factor). A 2,300 W load on a 230 V supply draws 10 A. Add up all the equipment on a circuit: amplifiers (consider average draw, not just the rated output), consoles, racks and lighting. Plan to use no more than about 80 per cent of a breaker’s rating and follow the electrical rules of the country. A three-phase supply has three live lines; spread loads across them so they are balanced, and keep audio and lighting on separate circuits where possible to reduce hum.
Voltage drop in a long cable is V = I x R, and the resistance of copper is about 0.0175 ohm mm2/m, so a two-core run of length L metres with cross-section A mm2 has R = 0.0175 x 2L / A.
3. Earthing and protection
Never remove the earth from mains equipment. Use RCDs (residual-current devices) for portable supplies. Inspect and test cables and equipment (in many places portable appliance testing is required). Keep power cables away from signal cables, and do not coil mains cable while powered if it carries a heavy load because it can overheat.
4. Loads overhead and on the stage
Loudspeakers may be flown from trusses or stacked on stages. Every item in the chain (motors, shackles, slings, bolts) has a working load limit (WLL). The sum of all loads (speakers plus rigging hardware) must stay below the lowest limit in the system. Flying is a job for a qualified rigger following manufacturer instructions and local rules. Stacked speakers must be strapped and placed on a stable surface.
5. Hearing protection
For crews and performers, use ear plugs with a flat response (“musician plugs”) for loud shows, and rest the ears. Remember lesson 2: 85 dBA for 8 hours and halving the time for each 3 dB. Provide protection for the crew where levels are high. Keep records of the levels you measure.
6. Paperwork
Collect a tech rider from each artist, make an input list (channel, instrument, microphone, stand, phantom), a stage plot, the monitor mixes and a patch list. Share them early and bring printed copies. Keep a show log of problems and fixes.
7. Power numbers in the shell
Lab: Current, load and voltage drop
Work out the current of 2,300 W at 230 V, the percentage load of 24 A on a 32 A breaker, the resistance of a 50 m two-core run of 2.5 mm2 and the total weight hanging from a line array.
Objectives
- Current in amps of a 2,300 W load on a 230 V supply.
- Percentage load of 24 A on a 32 A breaker.
- Resistance in ohms of a 50 m two-core run of 2.5 mm2 copper.
- Total kg of 8 speakers at 55 kg plus 40 kg of rigging.
(The outputs above are examples of the format. Real output varies by software version and setup.)
8. On your bench
- Add up the power draw of your rack and check each circuit is below 80 per cent.
- Mark the three phases and balance your loads.
- Measure the voltage at the end of a long cable run under load.
- Check every item in a rigging plan has a WLL above its load, and that a qualified rigger signs it off.
- Prepare an input list and a stage plot for your show.
9. Hands-on lab: Current, circuit load, phase balance, voltage drop and rigging load
10. Common mistakes
| Mistake | Better |
|---|---|
| Loading a circuit to 100 per cent | Plan for about 80 per cent |
| Removing the earth pin | Never; fix the real hum cause |
| Unbalanced phases | Spread loads across all three |
| Undersized long cable runs | Calculate voltage drop |
| Flying speakers without a qualified rigger | Rated hardware and a competent person |
| Forgetting rigging weight | Add hardware to the load |
| No hearing protection for the crew | Provide plugs |
11. Key takeaways
- I = P / V (divide also by power factor when needed).
- Plan for about 80 per cent of breaker rating and keep phases balanced.
- Voltage drop = I x R; copper is about 0.0175 ohm mm2/m.
- Overhead loads need a qualified rigger and rated hardware.
- Earth, RCD, hearing protection and paperwork are part of the job.
An amplifier rack delivers 4,000 W of output at 85 per cent efficiency on a 230 V supply. What current does it draw and is a 32 A breaker enough at 80 per cent?
Draw = 4000 / 0.85 = 4706 W. Current = 4706 / 230 = 20.5 A. 80 per cent of 32 A is 25.6 A, so a 32 A breaker is enough for this rack alone, with 5 A to spare for other equipment.
Can You Explain It?
Close the lesson and answer these without looking back. The goal isn't the wording — it's whether you've formed a usable mental model.
- Explain why circuits are planned at 80 per cent of the breaker rating.
- Describe what an RCD does.
- Say what a working load limit means for a flown system.
🧪 Want to practise this on your own computer? See how to set up your lab →